Skip to main content Skip to office menu Skip to footer
Capital IconMinnesota Legislature

Office of the Revisor of Statutes

4725.3250 PUMPS AND PUMPING EQUIPMENT.

A pump or pump base installed on a well must be constructed so no unprotected openings exist into the interior of the pump or well casing.

A.

A hand pump, hand pump head, stand, or similar device must have a closed and screened spout, directed downward. The pump must have a concrete slab at least four inches thick extending horizontally at least one foot in every direction from the well casing and sloped to divert water away from the casing. A watertight seal must be provided between the casing and the slab.

B.

A reciprocating pump rod must operate through a stuffing box, packing gland, or other watertight and vermin-proof fitting.

C.

An oil lubricated vertical turbine pump must not be installed in a well.

D.

A water lubricated vertical turbine pump must be lubricated with water from the well or a potable source.

History:

17 SR 2773; 33 SR 211

Published Electronically:

September 2, 2008

Official Publication of the State of Minnesota
Revisor of Statutes