IMC section 404.1 is amended to read as follows:
404.1 Enclosed parking garages. Mechanical ventilation systems for enclosed parking garages shall operate automatically upon detection of certain gas concentrations. Enclosed parking garages shall be equipped with a carbon monoxide (CO) detector and a nitrogen dioxide (NO2) detector. The mechanical ventilation system shall activate upon detection of a CO level of 25 parts per million (ppm) or greater, a NO2 level of 3 ppm or greater, or both. Such detectors shall be listed in accordance with UL 2075 and installed in accordance with their listing and manufacturers' instructions.
IMC section 404.2 is amended to read as follows:
404.2 Occupied spaces accessory to public garages. Connecting offices, waiting rooms, ticket booths, elevator lobbies, and similar uses that are accessory to a public garage shall be maintained at a positive pressure and shall be provided with ventilation in accordance with IMC section 403.3.
IMC section 404 is amended by adding a subsection 404.3 to read as follows:
404.3 Minimum exhaust. The mechanical ventilation system shall be capable of producing a minimum exhaust rate of 0.75 cfm per square foot (0.0038 m3/s·m2) of floor area.
IMC Section 404.4 is amended by adding a section to read as follows:
404.4 Prohibition of heated commercial parking garages. Commercial parking garages shall comply with the Minnesota Commercial Energy Code, chapter 1323.