4715.2400 PITCH ON HORIZONTAL DRAINAGE PIPING.
Horizontal drainage piping shall be installed in uniform alignment at uniform slopes in accordance with the following requirements and in no case at a slope which will produce a computed velocity of less than two feet per second, unless otherwise permitted by the administrative authority, based on hydraulic analysis of the piping system.
| Size of Piping | Minimum Slope |
| Less than 3 inches | 1/4 inch per foot |
| 3 inches to 6 inches | 1/8 inch per foot |
| 8 inches and over | 1/16 inch per foot |