1346.1206 SECTION 1206 PIPING INSTALLATION.
§
Subpart 1.
Section 1206.1.1.
IMC Section 1206.1.1 is amended to read as follows:
1206.1.1 Prohibited tee applications. Fluid in the supply side of a hydronic system shall not enter a tee fitting through the branch opening. Fluid from two returns shall not enter on the run of the same tee.
§
Subp. 3.
Section 1206.12.
IMC Section 1206 is amended by adding a new subsection to the end of the section to read as follows:
1206.12 Draining and venting. Hydronic pipes shall be installed so that the pipes can be drained and so that air can be completely removed from the system during filling.