1323.0681 SECTION 6.8, MINIMUM EQUIPMENT EFFICIENCY TABLES.

ASHRAE Standard 90.1, Table 6.8.1C, is amended to read:

TABLE 6.8.1C Water Chilling Packages - Minimum Efficiency Requirements

Equipment Type Size Category Subcategory or Rating Condition Minimum Efficienciesa Test Procedureb
Air Cooled, with Condenser, Electrically Operated All Capacities 2.80 COP 3.05 IPLV ARI 550/590
Air Cooled, without Condenser, Electrically Operated All Capacities 3.10 COP 3.45 IPLV
Water Cooled, Electrically Operated, Positive Displacement (Reciprocating) All Capacities 4.20 COP 5.05 IPLV ARI 550/590
Water Cooled, Electrically Operated, Positive Displacement (Rotary Screw and Scroll) <150 tons 4.45 COP 5.20 IPLV ARI 550/590
≥150 tons and <300 tons 4.90 COP 5.60 IPLV
≥300 tons 5.50 COP 6.15 IPLV
Water Cooled, Electrically Operated, Centrifugal <150 tons 5.00 COP 5.25 IPLV ARI 550/590
≥150 tons and <300 tons 5.55 COP 5.90 IPLV
≥300 tons 6.10 COP 6.40 IPLV
Air-Cooled Absorption Single Effectc All Capacities 0.60 COP ARI 560
Water-Cooled Absorption Single Effectc All Capacities 0.70 COP
Absorption Double Effect, Indirect-Fired All Capacities 1.00 COP 1.05 IPLV
Absorption Double Effect, Direct-Fired All Capacities 1.00 COP 1.00 IPLV

aThe chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is <40° F.

bSection 12 contains a complete specification of the referenced test procedure, including the reference year version of the test procedure.

cSee Section 6.9.1.