1323.0550 SECTION 5.5, PRESCRIPTIVE BUILDING ENVELOPE OPTION.

Subpart 1.

Roof insulation.

ASHRAE Standard 90.1, Section 5.5.3.1, is amended to read:

5.5.3.1 Roof insulation. All roofs shall comply with the insulation values specified in Tables 5.5-1 through 5.5-8. Skylight curbs shall be insulated to the level of roofs with insulation entirely above deck or R-5, whichever is less.

Subp. 2.

Table 5.5-6.

ASHRAE Standard 90.1, Table 5.5-6, Building Envelope Requirements for the Southern Minnesota Climate Zone is amended to read:

TABLE 5.5-6 Building Envelope Requirements For
Southern Minnesota Climate Zone (Zone 6)

Nonresidential Residential Semiheated
Opaque Elements Assembly Max. Insulation Min. R-Value Assembly Max. Insulation Min. R-Value Assembly Max. Insulation Min. R-Value
Roofs, Insulation
Entirely Above Deck U-0.043 R-23 ci U-0.043 R-23 ci U-0.06 R-16.6 ci
Metal Building U-0.043 R-30 U-0.043 R-30 U-0.06 R-19
Attic and Other U-0.027 R-30 U-0.027 R-30 U-0.06 R-19
Walls, Above Grade
Mass U-0.104 R-9.5 ci U-0.09 R-11.4 ci U-0.58 NR
Metal Building U-0.113 R-13 U-0.057 13 + R-13 U-0.113 R-13
Steel Framed U-0.084 R-13 ci + R-3.8 ci U-0.064 R-13 + R-7.5 ci U-0.124 R-13
Wood Framed and Other U-0.089 R-13 U-0.064 R-13 +
R-3.8 ci
U-0.089 R-13
Wall, Below Grade
Below- Grade Wall C-0.085 R-10 ci C-0.085 R-10 ci C-0.085 R-10 ci
Floors
Mass U-0.087 R-8.3 ci U-0.064 R-12.5 ci U-0.322 NR
Steel Joist U-0.038 R-30 U-0.038 R-30 U-0.069 R-13
Wood Framed and Other U-0.033 R-30 U-0.033 R-30 U-.0066 R-13
Slab-On-Grade Floors
Unheated F-0.520 R-10 to footing* F-0.520 R-10 to footing* F-0.520 R-10 to footing*
Heated F-0.520 R-10 to footing* F-0.520 R-10 to footing* F-0.520 R-10 to footing*
Opaque Doors
Swinging U-0.700 U-0.500 U-0.700
Non- swinging U-0.500 U-0.500 U-1.450
Fene- stration Assembly Max. U (Fixed/ Operable) Assembly Max. SHGC (All Orienta- tions/ North- Oriented) Assembly Max. U (Fixed/ Operable) Assembly Max. SHGC (All Orienta- tions/ North- Oriented) Assembly Max. U (Fixed Operable) Assembly Max. SHGC (All Orienta- tions/ North- Oriented)
Vertical Glazing, Percent of Wall
0-10.0 Ufixed -0.57 SHGCall
-0.49
Ufixed -0.57 SHGCall
-0.49
Ufixed -1.22 SHGCall
-NR
Uoper -0.67 SHGCnorth
-0.49
Uoper -0.67 SHGCnorth
-0.64
Uoper -1.27 SHGCnorth
-NR
10.1- 20.0 Ufixed -0.57 SHGCall
-0.39
Ufixed -0.57 SHGCall
-0.39
Ufixed -1.22 SHGCall
-NR
Uoper -0.67 SHGCnorth
-0.49
Uoper -0.67 SHGCnorth
-0.49
Uoper -1.27 SHGCnorth
-NR
20.1- 30.0 Ufixed -0.57 SHGCall
-0.39
Ufixed -0.57 SHGCall
-0.39
Ufixed -1.22 SHGCall
-NR
Uoper -0.67 SHGCnorth
-0.49
Uoper -0.67 SHGCnorth
-0.49
Uoper -1.27 SHGCnorth
-NR
30.1- 40.0 Ufixed -0.57 SHGCall
-0.39
Ufixed -0.57 SHGCall
-0.39
Ufixed -1.22 SHGCall
-NR
Uoper -0.67 SHGCnorth
-0.49
Uoper -0.67 SHGCnorth
-0.49
Uoper -1.27 SHGCnorth
-NR
40.1 -50.0 Ufixed -0.46 SHGCall
-0.26
Ufixed -0.46 SHGCall
-0.26
Ufixed -0.98 SHGCall
-NR
Uoper -0.47 SHGCnorth
-0.47
Uoper -0.47 SHGCnorth
-0.49
Uoper -1.02 SHGCnorth
-NR
Skylight, Percent of Roof
0-2.0 Uall -0.69 SHGCall
-0.49
Uall -0.58 SHGCall
-0.49
Uall -1.36 SHGCall
-NR
Greater than 2 to 5.0 Uall -0.69 SHGCall
-0.49
Uall -0.58 SHGCall
-0.39
Uall -1.36 SHGCall
-NR

*"To footing" means to the top of the footing if the insulation is on the exterior, or to the top of the slab if the insulation is on the interior.

Subp. 3.

Table 5.5-7.

ASHRAE Standard 90.1, Table 5.5-7, Building envelope requirements for the northern Minnesota climate zone is amended to read:

Nonresidential Residential Semiheated
Opaque Elements Assembly Max. Insulation Min. R-Value Assembly Max. Insulation Min. R-Value Assembly Max. Insulation Min. R-Value
Roofs, Insulation
Entirely Above Deck U-0.043 R-23 ci U-0.043 R-23 ci U-0.06 R-16.6 ci
Metal Building U-0.043 R-23 U-0.043 R-23 U-0.06 R-16.6
Attic and Other U-0.043 R-30 U-0.043 R-30 U-.06 R-19
Walls, Above Grade
Mass U-0.09 R-9.5 ci U-0.08 R-13.3 ci R-13.0 + R- U-0.58 NR
Metal Building U-0.057 R-13 U-0.057 R-13
R-13 + R-13
U-0.113 R-13
Steel Framed U-0.064 R-13 + R-3.8 ci U-0.064 R-13 + R-7.5 ci U-0.124 R-13
Wood Framed and Other U-0.089 R-13 U-0.051 R-13 + R-7.5 ci U-0.089 R-13
Walls, Below Grade
Below- Grade Wall C-0.085 R-10 ci C-0.085 R-10 ci C-0.085 R-10 ci
Floors
Mass U-0.087 R-8.3 ci U-0.064 R-12.5 ci U-0.137 R-4.2 ci
Steel Joist U-0.038 R-30 U-0.038 R-30 U-0.052 R-19
Wood Framed and Other U-0.033 R-30 U-0.033 R-30 U-.0066 R-13
Slab-On-Grade Floors
Unheated F-0.52 R-10 to footing* F-0.52 R-10 to footing* F-0.52 R-10 to footing*
Heated F-0.52 R-10 to footing* F-0.52 R-10 to footing* F-0.52 R-10 to footing*
Opaque Doors
Swinging U-0.70 U-0.50 U-0.70
Non- swinging U-0.50 U-0.50 U-1.45
Fene- stration Assembly Max. U (Fixed/ Operable) Assembly Max. SHGC (All Orienta- tions/ North- Oriented) Assembly Max. U (Fixed/ Operable) Assembly Max. SHGC (All Orienta- tions/ North- Oriented) Assembly Max. U (Fixed/ Operable) Assembly Max. SHGC (All Orienta- tions/ North- Oriented)
Vertical Glazing, Percent of Wall
0-10.0 Ufixed -0.57 SHGCall
-0.49
Ufixed -0.57 SHGCall
-0.49
Ufixed -1.22 SHGCall
-NR
Uoper -0.67 SHGCnorth
-0.64
Uoper -0.67 SHGCnorth
-0.64
Uoper -1.27 SHGCnorth
-NR
10.1- 20.0 Ufixed -0.57 SHGCall
-0.49
Ufixed -0.57 SHGCall
-0.49
Ufixed -1.22 SHGCall
-NR
Uoper -0.67 SHGCnorth
-0.64
Uoper -0.67 SHGCnorth
-0.64
Uoper -1.27 SHGCnorth
-NR
20.1- 30.0 Ufixed -0.57 SHGCall
-0.49
Ufixed -0.57 SHGCall
-0.49
Ufixed -1.22 SHGCall
-NR
Uoper -0.67 SHGCnorth
-0.64
Uoper -0.67 SHGCnorth
-0.64
Uoper -1.27 SHGCnorth
-NR
30.1- 40.0 Ufixed -0.57 SHGCall
-0.49
Ufixed -0.57 SHGCall
-0.49
Ufixed -1.22 SHGCall
-NR
Uoper -0.67 SHGCnorth
-0.64
Uoper -0.67 SHGCnorth
-0.64
Uoper -1.27 SHGCnorth
-NR
40.1 -50.0 Ufixed -0.46 SHGCall
-0.36
Ufixed -0.46 SHGCall
-0.36
Ufixed -0.98 SHGCall
-NR
Uoper -0.47 SHGCnorth
-0.64
Uoper -0.47 SHGCnorth
-0.64
Uoper -1.02 SHGCnorth
-NR
Skylight, Percent of Roof
0-2.0 Uall -0.69 SHGCall
-0.68
Uall -0.69 SHGCall
-0.64
Uall -1.36 SHGCall
NR
Greater than 2.1 to 5.0 Uall -0.69 SHGCall
-0.64
Uall -0.69 SHGCall
-0.64
Uall -1.36 SHGCall
-NR

*"To footing" means to the top of the footing if the insulation is on the exterior, or to the top of the slab if the insulation is on the interior.

Statutory Authority:

MS s 326B.02; 326B.101; 326B.106; 326B.13