Skip to main content Skip to office menu Skip to footer
Capital IconMinnesota Legislature

Office of the Revisor of Statutes

1322.1104 IRC SECTION N1104, MECHANICAL VENTILATION SYSTEMS.

IRC Chapter 11 is amended by adding a section to read as follows:

N1104.1 Mechanical ventilation requirements. A mechanical ventilation system shall be installed that meets the requirements of this section. This section covers the continuous and total mechanical ventilation requirements for dwelling unit ventilation at summer and winter climatic design conditions according to Section N1104.4.13 and chapter 1346. All unfinished basements, crawlspaces, and levels shall be provided with a minimum ventilation rate of 0.02 cfm per square foot, or a minimum of one supply duct and one return duct. The supply and return ducts shall be separated by one-half the diagonal dimension of the basement to avoid a short circuit of the air circulation.

Exception: Kitchen and bath fans that are not included as part of the mechanical ventilation system are exempt from the requirements of Section N1104 but shall comply with the IRC.

N1104.1.1 Additions or alterations to existing buildings. Additions or alterations to existing buildings shall require a dwelling unit mechanical ventilation system that meets Section N1104.

Exception: Buildings whose permit of initial construction was applied for prior to April 15, 2000, and did not require a dwelling unit mechanical ventilation system.

N1104.2 Total ventilation rate. The mechanical ventilation system shall provide sufficient outdoor air to equal the total ventilation rate average, for each one-hour period according to Table N1104.2, or Equation 11-1, based on the number of bedrooms and the square footage of conditioned space, including the basement but excluding conditioned crawl spaces. For heat recovery ventilators and energy recovery ventilators the average hourly ventilation capacity must be determined in consideration of any reduction of exhaust or outdoor air intake, or both, for defrost or other equipment cycling per HVI Standard 920.

Equation 11-1:
Total ventilation rate (cfm) = (0.02 x square feet of
conditioned space) +
[15 x (number of bedrooms + 1)]

N1104.2.1 Continuous ventilation. A minimum of 50 percent of the total ventilation rate, but not less than 40 cfm, shall be provided, on a continuous rate average for each one-hour period according to Table N1104.2 or Equation 11-2. The portion of the mechanical ventilation system that is intended to be continuous may have automatic cycling controls providing the average flow rate for each hour meeting the requirements of Section N1104.2.1.

Equation 11-2:
Continuous ventilation (cfm) = total ventilation rate/2

N1104.2.1.1 Ventilation rate. The continuous ventilation system shall be balanced in accordance with Section N1104.4.2.

Exception: If the local ventilation requirements according to IRC Section R303.3 are being met by the continuous ventilation system, it shall be capable of operating at a rate not more than 100 percent greater than required by Section N1104.2.1.

N1104.2.2 Intermittent ventilation. The difference between the total ventilation rate and the continuous ventilation rate shall be based on flow rates as designed or as installed.

Table N1104.2
Total and Continuous Ventilation Rates (in cfm)
Number of Bedrooms
1 2 3 4 5
Conditioned space¹ (in sq. ft.) Total/ Continuous Total/ Continuous Total/ Continuous Total/ Continuous Total/ Continuous Total/ Continuous
1000-1500 60/40 75/40 90/45 105/53 120/60 135/68
1501-2000 70/40 85/43 100/50 115/58 130/65 145/73
2001-2500 80/40 95/48 110/55 125/63 140/70 155/78
2501-3000 90/45 105/53 120/60 135/68 150/75 165/83
3001-3500 100/50 115/58 130/65 145/73 160/80 175/88
3501-4000 110/55 125/63 140/70 155/78 170/85 185/93
4001-4500 120/60 135/68 150/75 165/83 180/90 195/98
4501-5000 130/65 145/73 160/80 175/88 190/95 205/103
5001-5500 140/70 155/78 170/85 185/93 200/100 215/108
5501-6000² 150/75 165/83 180/90 195/98 210/105 225/113

1 Conditioned space includes the basement.

2 If conditioned space exceeds 6000 sq. ft. or there are more than 6 bedrooms, use Equation 11-1 from Section N1104.2 to calculate total ventilation rate.

N1104.3 Ventilation system requirements. The mechanical ventilation system shall be one of three types: exhaust according to Section N1104.3.1; balanced, and HRV/ERV according to Section N1104.3.2; or other method according to Section N1104.3.3.

N1104.3.1 Exhaust systems. Fans used to comply with the continuous ventilation part of the mechanical ventilation system shall:

1. meet the minimum continuous ventilation rate in Section N1104.2.1 at the point of discharge;

2. be designed and certified by the equipment manufacturer as capable of continuous operation at the rated cfm;

3. have a maximum 1.0 sone per HVI Standard 915 for surface mounted fans;

4. be permitted to use a required overcurrent protection device as a disconnect per the National Electric Code, incorporated by reference in Minnesota Rules, chapter 1315; and

5. comply with the Minnesota Mechanical Code, chapter 1346, which may require additional make-up air.

Fans used to comply with the intermittent ventilation part of the mechanical ventilation system shall have a maximum 2.5 sone per HVI Standard 915.

N1104.3.2 Balanced, and HRV/ERV systems. A heat recovery ventilator (HRV) or energy recovery ventilator (ERV) shall meet either:

1. the requirements of HVI Standard 920, 72 hours minus 13 degrees Fahrenheit cold weather test; or

2. certified by a registered professional engineer and installed per manufacturer's installation instructions.

An HRV or ERV intended to comply with both the continuous and total ventilation rate requirements shall meet the rated design capacity of the continuous ventilation rate in Section N1104.2.1 under low capacity and meet the total ventilation rate in Section N1104.2.2 under high capacity.

Exception: The balanced, and HRV/ERV system may include exhaust fans to meet the intermittent ventilation rate. Surface mounted fans shall have a maximum 2.5 sones per HVI Standard 915.

N1104.3.3 Other methods. Any mechanical ventilation system consisting of exhaust fans, supply fans, or a combination of both, complying with Section N1104, shall be allowed. A mechanical ventilation system specifically identified in Section N1104.3.1 or N1104.3.2 shall not conflict with Sections N1104.3.1 and N1104.3.2. For the purposes of this section, the delivered ventilation rate is the larger of the total air flow of the operating supply fans, or total air flow of the operating exhaust fans.

N1104.4 Installation requirements. All types of mechanical systems shall meet the requirements of this section. The mechanical ventilation system and its components shall also be installed according to the Mechanical Code, Minnesota Rules, chapter 1346, and the equipment manufacturer's installation instructions.

N1104.4.1 Air distribution and circulation. Outdoor air shall be delivered to each habitable space by a forced air circulation system, separate duct system, individual inlets, or a passive opening.

N1104.4.1.1 Forced air circulation systems. When outdoor air is supplied directly through a forced air circulation system, the requirements of this section shall be met by either:

(a) when an outdoor air supply is not ducted to the forced air system, controls shall be installed to allow the forced air system to provide an average circulation flow rate each hour, of not less than 0.15 cfm per square foot of the conditioned floor area; or

(b) when the outdoor air supply is ducted to the forced-air system, it shall be tempered so that the mixed air temperature shall be no less than 60 degrees Fahrenheit or the heating equipment manufacturer's installation instruction, and controls shall be installed to allow the forced air circulation system to provide an average flow rate not less than 0.075 cfm per square foot of conditioned floor area.

N1104.4.1.2 Directly ducted and individual room inlets. When outdoor air is supplied directly to habitable spaces with an airflow of 20 cfm or greater, the system shall be designed and installed to temper incoming air to not less than 40 degrees Fahrenheit measured at the point of distribution into the space.

Table N1104.4.1.1(1)
Indirect Circulation Air Flow Rates
for Forced-Air Circulation Systems (in cfm)
Forced-Air Circulation Systems Flow Rate (cfm)
600 800 1000 1200 1400 1600 1800 2000
Conditioned Floor Area Average Air Flow each Hr (cfm) Number of Minutes per Hour, if cycled
1000-1500 225 23 17 14 12 10 9 8 7
1501-2000 300 30 23 18 15 13 12 10 9
2001-2500 375 38 29 23 19 16 14 13 12
2501-3000 450 45 34 27 23 20 17 15 14
3001-3500 525 53 40 32 27 23 20 18 16
3501-4000 600 60 45 36 30 26 23 20 18
4001-4500 675 na¹ 51 41 34 29 26 23 21
4501-5000 750 na¹ 57 45 38 33 29 25 23
5001-5500 825 na¹ na¹ 50 42 36 31 28 25
5501-6000 900 na¹ na¹ 54 45 39 34 3 27

1 Not allowed

Table N1104.4.1.1(2)
Direct Distribution Air Flow Rates Using
Forced-Air Circulation Systems (in cfm)
Forced-Air Circulation Systems Flow Rate (cfm)
600 800 1000 1200 1400 1600 1800 2000
Conditioned Floor Area Average Air Flow each Hr (cfm) Number of Minutes per Hour, if cycled
1000-1500 115 13 9 7 6 5 5 4 4
1501-2000 150 15 13 9 8 7 6 5 5
2001-2500 190 19 15 13 10 8 7 7 6
2501-3000 225 23 17 14 13 10 9 8 7
3001-3500 265 27 20 15 14 13 10 9 8
3501-4000 300 30 23 18 15 13 13 10 9
4001-4500 340 34 26 21 17 15 13 13 11
4501-5000 375 38 24 23 19 17 15 13 13
5001-5500 415 42 32 25 21 18 16 14 13
5501-6000 450 45 34 27 23 20 17 15 14

N1104.4.1.3 Passive openings. When outdoor air is brought in through a passive opening, the maximum cfm of the outdoor air requirements shall be combined with the maximum makeup air requirements of Minnesota Rules, chapter 1346. The combined air rates shall be brought into the dwelling unit in accordance with chapter 1346. Controls shall be installed to distribute air throughout the dwelling unit as required by Section N1104.4.1.1a.

N1104.4.2 Airflow verification. Mechanical ventilation system airflows greater than 30 cfm at the building exhaust or intake shall be tested and verified using a flow hood, flow grid, pitot tube, or other airflow measuring device. The airflow verification results shall be made available to the building official upon request.

N1104.4.2.1 Airflow requirements. When the system is intended to be unbalanced, the design supply air flow shall not exceed 0.05 cfm per square foot of conditioned space. The operating exhaust air flow shall meet the requirements of Section N1104.3.1 and the Minnesota Mechanical Code, chapter 1346, which may require additional makeup air. When the system is intended to be balanced, the exhaust and supply airflows shall be within plus or minus ten percent of each other or the manufacturer's installation instructions, whichever is more restrictive.

N1104.4.3 Fans. When used as part of the mechanical ventilation system, fans shall be capable of delivering the designed air flow as determined by Section N1104.2 according to HVI Standard 916. Fans shall be designed and certified by the equipment manufacturer as capable of continuous operation at the rated cfm. Surface mounted fans used to comply with the continuous ventilation part of the mechanical ventilation system shall have a maximum 1.0 sone per HVI Standard 915. Fans used to comply with the intermittent ventilation part of the mechanical ventilation system shall have a maximum 2.5 sone per HVI Standard 915.

Exception: Sone requirements do not apply to forced air circulation systems and remotely mounted fans, provided the remotely mounted fan is not in a habitable space and there is at least 4 feet of ductwork between the fan and the grille.

N1104.4.4 Multifan systems. When two or more exhaust fans in a dwelling unit share a common exhaust duct, each fan shall be equipped with a backdraft damper to prevent recirculation of exhaust air into another room.

N1104.4.5 Connection to forced air circulation systems. Air ducts connected directly to the forced air circulation system can be used to meet the mechanical ventilation system requirements. Either the tempered outdoor air may be supplied to, or exhaust air may be drawn from, the forced air circulation system, but not both.

Exception: Both outdoor air and exhaust air may be connected to the forced air circulation system, provided that controls are installed to ensure that the forced air circulation system is operating whenever the mechanical ventilation system is operating or other means are provided to prevent short circuiting of fresh air according to the manufacturer's recommendations.

N1104.4.6 Dampers. Mechanical ventilation system supply and exhaust ducts shall be provided with accessible backflow dampers to minimize flow to or from the outdoors when the ventilation system is off.

N1104.4.7 Intake openings. Exterior air intake openings shall be accessible for inspection and maintenance. Intake openings shall be located in accordance with the Minnesota Mechanical Code, chapter 1346, and shall be covered with corrosion resistant screen of not less than one-fourth inch (6.4 mm) mesh. Intake openings shall be located at least 12 inches (305 mm) above adjoining grade level.

Exception: Combination air intake and exhaust hoods may be approved by the building official when specifically allowed by the equipment manufacturer's installation instructions.

N1104.4.8 Filtration. Mechanically supplied outdoor air shall have a filter with a designated minimum efficiency of MERV 4 as defined by ASHRAE Standard 52.2. The filter shall be located prior to the air entering the thermal conditioning components, blower, or habitable space and shall be installed to be readily accessible and facilitate regular service.

N1104.4.9 Noise and vibration. Mechanical ventilation system components shall be installed to minimize noise and vibration transmission. The equipment manufacturer's installation instructions shall be followed, and materials provided by the equipment manufacturer shall be used for this purpose. In the absence of specific materials or instructions, vibration dampening materials such as rubber grommets and flexible straps shall be used when connecting fans and heat exchangers to the building structure, and isolation duct connectors shall be used to mitigate noise transmission.

N1104.4.10 Controls. Mechanical ventilation system controls shall be provided according to the following.

1. Controls shall be installed to ensure that the forced air circulation system is operating whenever the mechanical ventilation system is operating if required by the equipment manufacturer's installation instructions.

2. Controls shall be installed to ensure that whenever the mechanical ventilation system is operating, the forced air circulation system provides indirect circulation of 0.15 cfm per square foot of conditioned floor area or direct distribution of 0.075 cfm per square foot of conditioned floor area.

3. If the mechanical ventilation system is not designed to operate whenever the forced air circulation system is operating, the mechanical ventilation system shall incorporate an accessible backflow damper to prevent flow from the outside when the mechanical ventilation system is off.

4. Controls shall be compatible with the mechanical ventilation system.

5. Controls shall be installed to operate the mechanical ventilation system as designed.

6. Controls shall be readily accessible to occupants and shall be labeled to indicate their function.

7. If a switch is used for continuous ventilation, it can be located centrally or remotely, but shall not be located in a bath or toilet room. If centrally located, it shall be properly labeled and lighted when the system is on. If remotely located, there shall be a lighted status indicator in a central location that will be lighted when the system is on.

N1104.4.11 Labeling. The outdoor air intake and exhaust air outlet shall include a permanent, weather resistant identification label stating "OUTDOOR AIR INTAKE" or "EXHAUST AIR OUTLET" as appropriate. Controls provided for continuous and intermittent ventilation shall be provided with a label stating "VENTILATION SYSTEM" or "VENTILATION FAN" or "INTERMITTENT FAN" or ventilation symbols, as appropriate.

N1104.4.12 Documentation. Mechanical ventilation systems shall be provided with documentation that includes proper operation and maintenance instructions and a warning regarding potential problems if the system is not operated and maintained. A permanent warning label shall be affixed to a mechanical ventilation system if it is readily accessible. If the mechanical ventilation system is not readily accessible, the documentation shall be in a conspicuous readily accessible location.

N1104.4.13 Climatic design conditions.

A. HVAC equipment must be sized according to the 2005 ASHRAE Handbook of Fundamentals, ACCA Manual J, or an equivalent method. Oversizing of heating equipment must not exceed 43 percent and cooling equipment must not exceed 21 percent.

B. Design conditions must be determined from Table N1104.4.13. Design condition adjustments may be made as determined by the building official to reflect local climates that differ from the tabulated temperatures or local weather experience.

TABLE N1104.4.13
Outdoor Design Conditions
City Summer Db/Wb °F Winter Db °F
Aitkin 82/72 -24
Albert Lea 85/72 -15
Alexandria 86/70 -21
Bemidji 84/68 -24
Cloquet 82/68 -20
Crookston 84/70 -27
Duluth 81/67 -20
Ely 82/68 -29
Eveleth 82/68 -26
Faribault 86/73 -16
Fergus Falls 86/71 -21
Grand Rapids 81/67 -23
Hibbing 82/68 -19
International Falls 83/67 -28
Litchfield 85/71 -18
Little Falls 86/71 -20
Mankato 86/72 -15
Minneapolis/St. Paul 88/72 -15
Montevideo 86/72 -17
Mora 84/70 -21
Morris 84/72 -21
New Ulm 87/73 -15
Owatonna 86/73 -16
Pequot Lake 84/68 -23
Pipestone 85/73 -15
Redwood Falls 89/73 -17
Rochester 85/72 -17
Roseau 82/70 -29
St. Cloud 86/71 -20
Thief River Falls 82/68 -25
Tofte 75/61 -14
Warroad 83/67 -29
Wheaton 84/71 -20
Willmar 85/71 -20
Winona 88/74 -13
Worthington 84/71 -14
Db = dry bulb temperature, degrees Fahrenheit
Wb = wet bulb temperature, degrees Fahrenheit

Statutory Authority:

MS s 326B.02; 326B.101; 326B.106; 326B.13

History:

33 SR 1480

Published Electronically:

June 17, 2009

Official Publication of the State of Minnesota
Revisor of Statutes