1311.0504 SECTION 504, FIRE ESCAPES.

IEBC section 504.4 is amended to read as follows:

504.4 Dimensions. Existing and replacement fire escape stairs shall meet the minimum width, capacity, riser height, and tread depth as specified in Table 504.4.

TABLE 504.4
DIMENSIONS FOR EXISTING AND REPLACEMENT FIRE ESCAPE STAIRS
Feature Serving More Than 10 Occupants Serving 10 or Fewer Occupants
Minimum Width 22 inches 18 inches
Maximum Riser Height 9 inches 12 inches
Minimum Tread Depth 9 inches 6 inches