1309.0702 SECTION R702, INTERIOR COVERING.

Subpart 1.

IRC Table R702.1(3).

Table R702.1(3) is amended to read as follows:

TABLE R702.1(3)

CEMENT PLASTER PROPORTIONS, PARTS BY VOLUME

CEMENTITIOUS MATERIALS
COAT CEMENT PLASTER TYPE Portland Cement Type I, II or III or Blended Cement Type IP, I(PM), IS or I(SM) Plastic Cement Masonry Cement Type M, S or N Lime VOLUME OF AGGREGATE PER SUM OF SEPARATE VOLUMES OF CEMENTI-
TIOUS MATERIALSb
Portland or blended 1 3/4 - 1-1/2a 2-1/2 - 4
First Masonry 1 2-1/2 - 4
Plastic 1 2-1/2 - 4
Portland or blended 1 3/4 - 1-1/2 3 - 5
Second Masonry 1 3 - 5
Plastic 1 3 - 5
Portland or blended 1 3/4 - 2 1-1/2 - 3
Finish Masonry 1 1-1/2 - 3
Plastic 1 1-1/2 - 3

For SI: 1 inch = 25.4 mm, 1 pound = 0.545 kg.

a. Lime by volume of 0 to 3/4 shall be used when the plaster will be placed over low-absorption surfaces such as dense clay tile or brick.

b. The same or greater sand proportion shall be used in the second coat than used in the first coat.

Subp. 2.

IRC section R702.7 Vapor retarders.

Section R702.7 is amended to read as follows:

R702.7 Vapor retarders. A Class I or II vapor retarder is required on the interior side of frame walls in Climate Zones 6 and 7. Class II vapor retarders are permitted only when specified on the construction documents.