To qualify as a gray water system, the system must meet or exceed the following requirements:
The liquid capacity of a gray water septic tank serving a dwelling must be based on the number of bedrooms existing and anticipated in the dwelling served and shall be at least as large as the capacities given in Table X.
| TABLE X | ||||
| Number of bedrooms (gallons) | Tank liquid capacity | |||
| 3 or less | 750 | |||
| 4 or 5 | 1,000 | |||
| 6 or 7 | 1,250 | |||
| 8 or 9 | 1,500 | |||
For ten or more bedrooms, the gray water septic tank shall be sized as: (1,500 + ((# of bedrooms - 9) x 150)).