Skip to main content Skip to office menu Skip to footer
Capital IconMinnesota Legislature

Office of the Revisor of Statutes

4714.0421 FIXTURES AND FIXTURE FITTINGS FOR PERSONS WITH DISABILITIES.

UPC section 421.2 is amended to read as follows:

421.2 Limitation of Hot Water Temperature for Public Lavatories. Hot water delivered from public-use lavatories shall be limited to a maximum temperature of 110º F (43º C) by a device that is in accordance with ASSE 1070 or CSA B125.3. The water heater thermostat shall not be considered a control for meeting this provision.

Statutory Authority:

MS s 326B.43; 326B.435

History:

40 SR 71

Published Electronically:

January 25, 2016

Official Publication of the State of Minnesota