1513.1100 MINIMUM FLOW RATES.

Pressure relief valves for excessive heat or fire protection used on containers covered by parts 1513.0300 to 1513.0380 and 1513.1000 to 1513.1070 must be constructed to discharge at not less than the rates required in this part before the pressure is in excess of 121 percent of the maximum allowable working pressure of the container. Relief protection for any other reason, except refrigerated storage, must use ASME UG-125 through UG-136.

Surface
Area,
Sq.Ft.
Flow Rate,
CFM
Air
Surface
Area,
Sq.Ft.
Flow Rate,
CFM
Air
Surface
Area,
Sq.Ft.
Flow Rate,
CFM
Air
20 258 185 1,600 900 5,850
25 310 190 1,640 950 6,120
30 360 195 1,670 1,000 6,380
35 408 200 1,710 1,050 6,640
40 455 210 1,780 1,100 6,900
45 501 220 1,850 1,150 7,160
50 547 230 1,920 1,200 7,410
55 591 240 1,980 1,250 7,660
60 635 250 2,050 1,300 7,910
65 678 260 2,120 1,350 8,160
70 720 270 2,180 1,400 8,410
75 762 280 2,250 1,450 8,650
80 804 290 2,320 1,500 8,900
85 845 300 2,380 1,550 9,140
90 885 310 2,450 1,600 9,380
95 925 320 2,510 1,650 9,620
100 965 330 2,570 1,700 9,860
105 1,010 340 2,640 1,750 10,090
110 1,050 350 2,700 1,800 10,330
115 1,090 360 2,760 1,850 10,560
120 1,120 370 2,830 1,900 10,800
125 1,160 380 2,890 1,950 11,030
130 1,200 390 2,950 2,000 11,260
135 1,240 400 3,010 2,050 11,490
140 1,280 450 3,320 2,100 11,720
145 1,310 500 3,620 2,150 11,950
150 1,350 550 3,910 2,200 12,180
155 1,390 600 4,200 2,250 12,400
160 1,420 650 4,480 2,300 12,630
165 1,460 700 4,760 2,350 12,850
170 1,500 750 5,040 2,400 13,080
175 1,530 800 5,300 2,450 13,300
180 1,570 850 5,590 2,500 13,520

Surface Area = Total Outside Surface Area of Container in Square Feet. If the surface area is not stamped on the nameplate or when the marking is not legible, the area can be calculated by using one of the following formulas:

(1) Cylindrical container with hemispherical heads
Area = overall length in feet times outside diameter in feet times 3.1416.
(2) Cylindrical container with other than hemispherical heads
Area = (overall length in feet plus 0.3 outside diameter in feet) times outside diameter in feet times 3.1416.
(3) Spherical container
Area = outside diameter in feet squared times 3.1416.

Flow Rate--CFM Air = cubic feet per minute of air required at standard conditions, 60 degrees Fahrenheit and atmospheric pressure (14.7 psia).

The rate of discharge may be interpolated for intermediate values of surface area. For containers with total outside surface area greater than 2,500 square feet, the required flow rate can be calculated using the formula, Flow Rate CFM Air = 22.11 A0.82 where A = outside surface of the container in square feet.

CONVERSION FACTORS:
ft2 x 0.092 903 = m2
CFM x 0.028 317 = m3/min
ft x 0.304 8 = m