Minnesota Administrative Rules
1513.0230 ELECTRICAL EQUIPMENT AND WIRING.
§
Subpart 1.
Ammonia installations.
Electrical equipment and wiring for use in ammonia installations must be general purpose or weather resistant as appropriate.
§
Subp. 2.
High concentrations of ammonia.
Where concentrations of ammonia in air in excess of 16 percent by volume are likely to be encountered, electrical equipment and wiring must be installed to comply with the requirements for use in hazardous locations, Class I, Group D, of NFPA 70, National Electrical Code, Articles 500 and 501.
Statutory Authority:
MS s 18C.121
History:
21 SR 277
Published Electronically:
September 10, 2007
Official Publication of the State of Minnesota
Revisor of Statutes