1370.0210 ILLUMINATION.
§
Subpart 1.
Minimum illumination.
At least five foot candles of illumination must be provided at floor level inside the storm shelter and at exits.
§
Subp. 2.
Source.
An emergency lighting system must be supplied from storage batteries or an on-site generator installed in accordance with the requirements of chapter 1315.
History:
12 SR 2251; L 2007 c 140 art 4 s 61; art 13 s 4; L 2008 c 337 s 64; 35 SR 1427