1305.0909 SECTION 909, SMOKE CONTROL SYSTEMS.

Subpart 1.

[F] Section 909.4.

IBC [F] Section 909.4 is amended by adding a subsection to read as follows:

909.4.7 Door opening force. With any of the design methods allowed by Section 909, the door opening force, latch release, and set-in-motion force shall comply with Section 1008.1.2 requirements when the system is in smoke control mode.

Subp. 2.

[F] Section 909.21.

IBC [F] Section 909 is amended by adding a subsection to read as follows:

909.21 High-rise and covered mall smoke-exhaust systems. High-rise buildings and covered mall buildings exceeding 50,000 square feet (4645 m2) in floor area, excluding anchor stores, shall be equipped with a post-fire smoke exhaust system installed and maintained in accordance with Section 913.