1305.0403 SECTION 403, HIGH-RISE BUILDINGS.
§
Subp. 3.
IBC section 403.4.8.2.
IBC section 403.4.8.2 is amended to read as follows:
403.4.8.2 Standby power loads. The following are classified as standby power loads:
1. Power and lighting for the fire command center required by Section 403.4.6;
2. Ventilation and automatic fire detection equipment for smokeproof enclosures; and
3. Passenger elevators serving occupied floors more than 75 feet (22860 mm) above the lowest level of fire department vehicle access.