4714.0717 SIZE OF BUILDING SEWERS.

UPC section 717, Table 717.1, is amended to read as follows:

TABLE 717.1
Maximum/Minimum Fixture Unit Loading on Building Sewer Piping
Size of Pipe (inches) SLOPE (inches per foot)
1/16 1/8 1/4
6 and smaller (As specified in Table 703.2/No minimum loading)
8* 1950/1500 2800/625 3900/275
10* 3400/1600 4900/675 6800/300
12* 5600/1700 8000/725 11 200/325

*Loadings less than the listed minimums must be approved by the Authority Having Jurisdiction.

For SI units: 1 inch = 25 mm, 1 inch per foot = 83.3 mm/m

Statutory Authority:

MS s 326B.43; 326B.435

History:

40 SR 71; 45 SR 1007