4715.2400 PITCH ON HORIZONTAL DRAINAGE PIPING.

Horizontal drainage piping shall be installed in uniform alignment at uniform slopes in accordance with the following requirements and in no case at a slope which will produce a computed velocity of less than two feet per second, unless otherwise permitted by the administrative authority, based on hydraulic analysis of the piping system.

Size of Piping Minimum Slope
Less than 3 inches 1/4 inch per foot
3 inches to 6 inches 1/8 inch per foot
8 inches and over 1/16 inch per foot